Directive 2012/49 - Amendment of Annex II to Directive 2006/87/EC laying down technical requirements for inland waterway vessels - Main contents
10.1.2013 |
EN |
Official Journal of the European Union |
L 6/49 |
COMMISSION DIRECTIVE 2012/49/EU
of 10 December 2012
amending Annex II to Directive 2006/87/EC of the European Parliament and of the Council laying down technical requirements for inland waterway vessels
(Text with EEA relevance)
THE EUROPEAN COMMISSION,
Having regard to the Treaty on the Functioning of the European Union,
Having regard to Directive 2006/87/EC of the European Parliament and of the Council of 12 December 2006 laying down technical requirements for inland waterway vessels and repealing Council Directive 82/714/EEC (1), and in particular the first sentence of Article 20(1) first subparagraph thereof,
Whereas:
(1) |
Since the adoption of the Directive 2006/87/EC, amendments to the Rhine Vessel Inspection Regulation have been agreed pursuant to Article 22 of the Revised Convention for Rhine Navigation. |
(2) |
It should be ensured that the Community inland navigation certificate and the vessel certificate delivered in accordance with Article 22 of the Revised Convention for Rhine Navigation are issued on the basis of technical requirements which guarantee an equivalent level of safety. |
(3) |
In order to avoid distortions of competition as well as different levels of safety, the amendments to Directive 2006/87/EC should enter into force as quickly as possible. |
(4) |
Directive 2006/87/EC should therefore be amended accordingly. |
(5) |
The measures provided for in this Directive are in accordance with the opinion of the Committee referred to in Article 7 of Council Directive 91/672/EEC of 16 December 1991 on the reciprocal recognition of national boatmasters’ certificates for the carriage of goods and passengers by inland waterway (2), |
HAS ADOPTED THIS DIRECTIVE:
Article 1
Directive 2006/87/EC is amended in accordance with the Annex to this Directive.
Article 2
Member States which have inland waterways as referred to in Article 1(1) of Directive 2006/87/EC shall bring into force the laws, regulations and administrative provisions necessary to comply with this Directive at the latest by 1 December 2013. They shall forthwith communicate to the Commission the text of those provisions.
When Member States adopt those provisions, they shall contain a reference to this Directive or be accompanied by such a reference on the occasion of their official publication. Member States shall determine how such reference is to be made.
Article 3
This Directive shall enter into force on the day of its publication in the Official Journal of the European Union.
Article 4
This Directive is addressed to the Member States which have inland waterways as referred to in Article 1(1) of Directive 2006/87/EC.
Done at Brussels, 10 December 2012.
For the Commission
The President
José Manuel BARROSO
ANNEX
Annex II to Directive 2006/87/EC is amended as follows:
(1) |
the list of contents is amended as follows:
|
(2) |
the following Chapter 14a is inserted: ‘CHAPTER 14a ON-BOARD SEWAGE TREATMENT PLANTS ON PASSENGER VESSELS Article 14a.01 Definitions For the purposes of this Chapter:
Article 14a.02 General provisions
Article 14a.03 Application for type approval
Article 14a.04 Type approval procedure
Article 14a.05 Amendment of type approvals
Article 14a.06 Conformity
Article 14a.07 Acceptance of equivalent approvals Member States can recognize type approvals for on-board sewage treatment systems based on different standards for the use on their national waterways. These type approvals should be notified to the Commission. Article 14a.08 Checking of serial numbers
Article 14a.09 Conformity of production
Article 14a.10 Non-conformity with the type-approved on-board sewage treatment plant type
Article 14a.11 Random sample measurement/Special test
Article 14a.12 Competent authorities and technical services Member States shall notify the Commission of the names and addresses of the competent authorities and technical services responsible for carrying out the functions outlined in this Chapter. The technical services shall satisfy the European standard on general requirements for the competence of testing and calibration laboratories (EN ISO/IEC 17025: 2005 - 8), taking the following conditions into account:
|
(3) |
Article 15.14(1) is replaced by the following:
|
(4) |
in the table of Article 24.02(2) the following entries relating to Chapter 14a are inserted after the entries for Chapter 12:
|
(5) |
in the table of Article 24.06(5) the following entries relating to Chapter 14a are inserted after the entries for Chapter 11:
|
(6) |
in the table of Article 24a.02(2) the following entries relating to Chapter 14a are inserted after the entry for Chapter 12:
|
(7) |
the following appendices VI to VII are added: ‘ Appendix VI On-board sewage treatment plants - Supplementary provisions and certificate models Table of contents PART I Supplementary provisions
PART II Information document (model)
PART III Type approval certificate (model)
PART IV Type approvals numbering system PART V Summary of type approvals for on-board sewage treatment plant types (model) PART VI Summary of on-board sewage treatment plants manufactured (model) PART VII Data sheet for on-board sewage treatment plants with type approval (model) PART VIII On-board sewage treatment plant parameters record for special test (model)
PART IX Equivalent type-approvals PART I Supplementary provisions
The procedure for testing an on-board sewage treatment plant is laid down in Appendix VII.
PART II (MODEL) Information document No relating to type approval of on-board sewage treatment plants intended for installation in inland waterway vessels On-board sewage treatment plant type: …
0.1 Make (manufacturer’s company name): … 0.2 Manufacturer’s designation for the on-board sewage treatment plant type: … … 0.3 Manufacturer’s type code corresponding to the information given on the on-board sewage treatment plant: … … 0.4 Manufacturer’s name and address: … Name and address of manufacturer’s authorised representative, if any: … … 0.5 Position, coding and method of attachment of the on-board sewage treatment plant’s serial number: … … 0.6 Position and method of attachment of the type approval number: … … 0.7 Address(es) of production works: … … Annexes:
10.1. Instructions for manual operation of the on-board sewage treatment plant 10.2. Notes on excess sludge management (discharge intervals) 10.3. Notes on maintenance and repair 10.4. Notes on action necessary in the case of stand-by operation of the on-board sewage treatment plant 10.5. Notes on action necessary in the case of emergency operation of the on-board sewage treatment plant 10.6. Notes on run-down, standstill and restart operation of the on-board sewage treatment plant 10.7. Notes on requirements for pre-treatment of galley waste water
Date, signature of on-board sewage treatment plant manufacturer … … Addendum Main characteristics of the on-board sewage treatment plant type (MODEL)
1.1 Manufacturer: … 1.2 Serial number of the plant: … 1.3 Mode of treatment: biological or mechanical/chemical (6 10 15) 1.4 Upstream waste water storage tank? Yes, … m3/No4
2.1 … 2.2 …
3.1 Maximum daily volumetric flow rate of sewage Qd (m3/d): … 3.2 Daily BOD5 pollution load (kg/d): … PART III Type approval certificate (MODEL) Seal of the competent authority Type approval No: … Extension No: … Notification of issuance/extension/refusal/withdrawal (7) of type approval for an on-board sewage treatment plant type in accordance with Directive 2006/87/EC Reason for extension, if applicable: … Section I
0.1 Make (manufacturer’s company name): … 0.2 Manufacturer’s designation for the on-board sewage treatment plant type: … … 0.3 Manufacturer’s type code corresponding to the information affixed to the on-board treatment plant: … … Position: … Method of attachment: … 0.4 Manufacturer’s name and address: … … Name and address of manufacturer’s authorised representative, if any: … … 0.5 Position, coding and method of attachment of the serial number of the on-board sewage treatment plant: … … … 0.6 Position and method of attachment of the type approval number: … … 0.7 Address(es) of production works: … … Section II
1.1 Particularities to be observed when installing the on-board sewage treatment plant in a craft: … 1.1.1 … 1.1.2 …
… …
The type approval is issued/extended/refused/withdrawn (9): Place: … Date: … Signature: … Appendices: Information folder Test results (see Annex 1) Addendum Test results for type approval (MODEL)
0.1 Make (manufacturer’s company name): … 0.2 Manufacturer’s designation for the on-board sewage treatment plant type: …
1.1 Inflow values 1.1.1 Daily volumetric flow rate of sewage Qd (m3/d): … 1.1.2 Daily BOD5 pollution load (kg/d): … 1.2 Purification efficiency 1.2.1 Evaluation of outflow values Evaluation of outflow values BOD5 (mg/l)
Evaluation of outflow values COD (mg/l)
Evaluation of outflow values TOC (mg/l)
Evaluation of outflow values SRF (mg/l)
1.2.2 Purification efficiency (elimination efficiency) (%)
1.3 Further parameters measured 1.3.1 Additional inflow and outflow parameters:
1.3.2 The following operating parameters are — when available — to be recorded during sampling:
1.3.3 Further operating parameters according to the manufacturer’s operating instructions … … … … 1.4 Competent authority or technical service: Place, date: … Signature: … PART IV Type-approvals numbering system
The number shall consist of four sections separated by the “*” character. Section 1 The small letter “e” followed by the distinguishing number of the State issuing the type-approval:
Section 2 The indication of the requirement level. The requirements regarding purification efficiency are likely to be stepped up in the future. The different requirement levels are denoted by Roman numerals, starting at level I. Section 3 A four-digit sequential number (with leading zeroes as applicable) to denote the base type-approval number. The sequence shall start from 0001. Section 4 A two-digit sequential number (with leading zero if applicable) to denote the extension. The sequence shall start from 01 for each number.
PART V Summary of type approvals for on-board sewage treatment plant types (MODEL) Seal of the competent authority List No: … Period from … to …
PART VI (MODEL) Summary of on-board sewage treatment plants manufactured Seal of the competent authority List No: … For the period from: … to: … The following information is supplied relating to on-board sewage treatment plant types and type approval numbers of on-board sewage treatment plants manufactured within the above period in accordance with the provisions of Directive 2006/87/EC: Make (manufacturer’s company name): … Manufacturer’s designation for the on-board sewage treatment plant type: … … Type approval number: … Date of issue: … Date of first issue (in the case of extensions): … Serial number of the on-board sewage treatment plant:
PART VII Data sheet for on-board sewage treatment plants with type approval (MODEL) Seal of the competent authority
PART VIII On-board sewage treatment plant parameters record for special test (MODEL)
1.1 Particulars of the on-board sewage treatment plant 1.1.1 Make: … 1.1.2 Manufacturer’s designation: … … 1.1.3 Type approval number: … 1.1.4 Serial number of the on-board sewage treatment plant: … … 1.2 Documentation The on-board sewage treatment plant shall be tested and the test results recorded on separate sheets which shall be individually numbered, signed by the inspector and attached to this record. 1.3 Testing Testing shall be carried out on the basis of the manufacturer’s guide to checking the components and parameters of the on-board treatment plant relevant to sewage treatment in accordance with Article 14a.01(10). In justified individual cases inspectors may at their own discretion dispense with checking certain plant components or parameters. During the test at least one random sample shall be taken. The results of the random sample measurement shall be compared with the control values set out in Article 14a.02(2), Table 2. 1.4 This test report, together with the attached records, comprises a total of … (14)… pages.
This is to certify that the on-board sewage treatment plant tested does not diverge to an inadmissible extent from the parameters and control values for operation specified in Article 14a.02(2), Table 2 are not exceeded. Name and address of inspection body: … … … Name of inspector: … Place and date: … Signature: … Test recognised by competent authority: … … … Place and date: … Signature: … Seal of the competent authority Name and address of inspection body: … … … Name of inspector: … Place and date: … Signature: … Test recognised by competent authority: … … … Place and date: … Signature: … Seal of the competent authority Name and address of inspection body: … … … Name of inspector: … Place and date: … Signature: … Test recognised by competent authority: … … … Place and date: … Signature: … Seal of the competent authority Addendum Appendix to the on-board sewage treatment plant parameters record (MODEL) Name of vessel: … Unique European Vessel Identification Number: … Manufacturer: … Plant type: … (Make/trademark/manufacturer’s trade name) (Manufacturer’s designation) Type approval No: … Year of construction of on-board sewage treatment plant: … Serial number of on-board sewage treatment plant: … Site of installation: … (Serial number) The on-board sewage treatment plant and its treatment-relevant components were identified from the data plate. The test was carried out on the basis of the manufacturer’s guide to checking the plant components and parameters relevant to sewage treatment. (A) Component testing Additional treatment-relevant components which are listed in the manufacturer’s guide to checking the plant components and parameters relevant to sewage treatment or Part II Annex 4 are to be entered here.
(B) Results of random sample measurement:
(C) Comments: … (The following deviating settings, modifications or alterations to the installed on-board sewage treatment plant were found.) … … … … … … Name of inspector: … Place and date: … Signature: … PART IX Equivalent type-approvals Type approvals in Resolution 2010-II-27 of the Central Commission for the Navigation on the Rhine of 9 December 2010 Appendix VII On-board sewage treatment plant Test procedure 1 GENERAL 1.1 Basics The test specification shall be used to verify the suitability of on-board sewage treatment plants on passenger vessels. In this procedure, the process and treatment technology used shall be examined and approved by means of a test plant. Conformity of the test plant with the treatment plants in service later is assured by applying identical design and dimensioning criteria. 1.2. Responsibility and test location The test plant for a range of on-board sewage treatment plant types shall be tested by a technical service. The test conditions at the test site are the responsibility of the technical service and must correspond to the conditions specified here. 1.3 Documents to be submitted The test shall be carried out on the basis of the information document in accordance with Appendix VI, Part II. 1.4 Plant dimensioning specifications The on-board sewage treatment plants shall be dimensioned and designed such that the limit values specified in Article 14a.02(2), Tables 1 and 2 in their outflow are not exceeded in the course of their operation. 2 MEASURES PREPARATORY TO TESTING 2.1 General Prior to commencement of the test the manufacturer shall supply the technical service with structural and process specifications of the test plant, to include a complete set of drawings and supporting calculations in accordance with Appendix VI, Part II, and shall provide full information on the on-board sewage treatment plant’s requirements in terms of installation, operation and maintenance. The manufacturer shall supply the technical service with information on the mechanical, electrical and technical safety of the on-board sewage treatment plant to be tested. 2.2 Installation and putting into service For the purpose of the test, the manufacturer shall install the test plant in such a way as to correspond to the intended installation conditions on board passenger vessels. Prior to testing the manufacturer must assemble the on-board sewage treatment plant and put it into service. Start-up must be in accordance with the manufacturer’s operating instructions and shall be checked by the technical service. 2.3 Run-in phase The manufacturer shall notify the technical service of the nominal duration of the run-in phase up to normal operation in weeks. The manufacturer shall specify the point where the run-in phase is deemed to be complete and testing may commence. 2.4 Inflow characteristics Domestic raw sewage shall be used for testing the test plant. The inflow characteristics as regards pollutant concentrations shall be obtained from the on-board sewage treatment plant manufacturer’s dimensioning documentation in accordance with Appendix VI, Part II by forming the quotient for the flow rate of organic substances in the form of a BOD5 load in kg/d and the design flow rate of sewage Qd in m3/d. The inflow characteristics shall be set accordingly by the inspection body. Formula 1 Calculation of the inflow characteristics Should application of formula 1 result in a lower average BOD5 concentration of less than CBOD5mean = 500 mg/l, at least a mean BOD5 concentration in the inflow water of CBOD5,min = 500 mg/l shall be set. The technical service must not break up the inflowing raw sewage in a comminatory. Removal of sand (e.g. by screening out) is permissible.
3.1 Loading phases and hydraulic feeding The test period shall comprise 30 test days. The test plant shall be fed on the test field with domestic waste water in accordance with the loading specified in Table 1. Various loading phases shall be covered, with the test sequence taking account of normal loading phases and special loading phases such as overload, underload and stand-by operation. The duration of each loading phase (number of test days) is set out in Table 1. The mean daily hydraulic load for each loading phase shall be set in accordance with Table 1. The mean pollutant concentration, to be set in accordance with point 2.4, shall be kept constant. Table 1 Load settings for each loading phase
The special load phases overload, underload and stand-by operation shall be carried out consecutively without interruption; the normal load phase shall be divided into several part phases. The test shall start and end with a normal load phase, of at least five days’ duration in each case. Daily hydraulic feeding hydrographs shall be set, depending on the specified operation of the on-board sewage treatment plant. The daily hydraulic feeding hydrograph shall be selected in accordance with the plant operation concept for the on-board sewage treatment plant. A distinction shall be made according to whether the on-board treatment plant is to be operated with or without an upstream sewage storage tank. The feeding hydrographs (daily hydrographs) are shown in Figure 1 and Figure 2. Throughout the entire test period the hourly inflow must remain constant. The mean hourly volumetric flow rate of sewage Qh,mean is equivalent to 1/24 of the daily hydraulic load according to Table 1. The inflow shall be measured continuously by the technical service. The daily hydrograph must keep within a ± 5 % tolerance. Figure 1 Daily hydrograph for feeding of on-board sewage treatment plant with upstream sewage storage tank Figure 2 Daily hydrograph for feeding of on-board sewage treatment plant without upstream sewage storage tank 3.2 Interruption or cancellation of the test It may be necessary to interrupt the test if the test plant can no longer be operated properly due to power failure or the malfunction of a subassembly. The test may be interrupted for the duration of the repair. In such cases it is not necessary to repeat the whole of the test, only the loading phase in which the subassembly malfunction took place. After the test is interrupted for a second time, the technical service shall decide whether the test may be continued or must be cancelled. The grounds for the decision must be stated and documented in the test report. Should the test be cancelled it must be repeated in full. 3.3 Examinations of purification efficiency and compliance with outflow limit values The technical service shall take samples from the inflow to the test plant and analyse them in order to confirm conformity with the inflow characteristics. Sewage samples shall be taken from the outflow of the test plant and analysed to determine the purification efficiency and compliance with the required outflow limit values. Sampling carried out shall include both simple random samples and 24h composite samples. In the case of the 24h composite samples, either time-proportional or flow-proportional sampling may be carried out. The type of 24h composite sample shall be specified by the inspection body. Sampling in the inflow and outflow shall be carried out simultaneously and to the same degree. In addition to the control parameters BOD5, COD and TOC the following parameters for inflow and outflow shall be measured in order to describe and represent the environmental and test conditions:
The number of examinations varies according to the relevant loading phase and is set out in Table 2. The number of samplings relates to the inflow or outflow of the test plant. Table 2 Specification of the number and timing of samplings in the inflow and outflow of the test plant
Where applicable, the following operating parameters shall also be measured from the random samples taken:
3.4 Evaluation of examinations In order to document the determined purification efficiency and to check adherence to process limit values, the minimum sample value (Min), the maximum sample value (Max) and the arithmetical mean (Mean) shall be specified as well as the individual measurement results for control parameters BOD5, COD and TOC. The loading phase shall also be given for the maximum sample value. Evaluations shall be carried out for all loading phases jointly. The results shall be processed as shown in the following table: Table 3a Specification for the statistical processing of data gathered — evaluation to document compliance with outflow limit values
Table 3b Specification for the statistical processing of data gathered — evaluation to document purification efficiency
The remaining parameters in accordance with 3.3(b) to (d) and the operating parameters in accordance with 3.3 shall be summarised in a table specifying the minimum sample result (Min), the maximum sample result (Max) and the arithmetical mean (Mean). 3.5 Compliance with the requirements of Chapter 14a The limit values in accordance with Article 14a.02(2) Tables 1 and 2 shall be deemed to be upheld, when each value for the parameters COD, BOD5 and TOC:
3.6 Operation and maintenance during testing Throughout the testing the test plant shall be operated in accordance with the manufacturer’s specifications. Routine checks and maintenance work shall be carried out in compliance with the manufacturer’s operation and maintenance instructions. The excess sludge generated by the biological purification process may only be removed from the on-board sewage treatment plant if this is specified by the manufacturer in their operation and maintenance instructions. All maintenance work carried out shall be recorded by the technical service and documented in the test report. During the test no unauthorised persons may have access to the test plant. 3.7 Sample analysis/analysis method The parameters to be studied shall be analysed using approved standard procedures. The standard procedure applied shall be specified. 4 TEST REPORT
Examples of test sequences Example 1 Example 2
Notes on determining biochemical oxygen demand after five days (BOD5) in 24h composite samples The International Standards ISO 5815 and 5815-2: 2003 stipulate that in order to carry out the analysis to determine biochemical oxygen demand after five days water samples should be stored immediately after sampling and up to the time of analysis in a brim-full, tightly sealed bottle at a temperature of 0–4 °C. The process of determining BOD5 should be initiated as soon as possible or at least within twenty-four hours of completion of sampling. In order to prevent biochemical degradation processes starting in the 24h composite sample, in practice the water sample is cooled to a maximum of 4 °C while sampling continues, and is stored at this temperature once the sampling process is complete. Suitable sampling equipment is commercially available. ’ |
-
Member States may implement equivalent procedures.
-
Instead of the chemical oxygen demand (COD) the total organic carbon (TOC) may also be referred to for the check.
-
Member States may implement equivalent procedures.
-
Instead of the chemical oxygen demand (COD) the total organic carbon (TOC) may also be referred to for the check.
-
Operating phases
The following operating phases shall be defined for testing:
(a) |
Stand-by operation is when the on-board sewage treatment plant is running but has not been fed with sewage for more than a day. An on-board sewage treatment plant may be in stand-by operation when, for example, the passenger vessel is not in service for an extended period and sits idle at its mooring. |
(b) |
Emergency operation is when individual subassemblies of an on-board sewage treatment plant have malfunctioned, so that the sewage cannot be treated as intended. |
(c) |
Run-down, standstill and restart operation is when an on-board sewage treatment plant is taken out of service for an extended period (winter mooring) and the power supply is switched off, or when the on-board sewage treatment plant is started up again at the beginning of the season. |
-
Specify as appropriate.
-
Specify as appropriate.
-
In case tests are made by the competent authority mark “not relevant”.
-
Specify as appropriate.
-
In case of more test cycles indicate for each cycle.
-
No limit values exist for the inflow.
-
Relevant type-approval certificate.
-
Specify as appropriate.
-
To include by tester.
-
Specify as appropriate.
-
Place a cross in the appropriate box.
-
No limit values exist for the inflow.
This summary has been adopted from EUR-Lex.