Regulation 2007/1497 - Commission Regulation 1497/2007 establishing, pursuant to Regulation 842/2006, standard leakage checking requirements for stationary fire protection systems containing certain fluorinated greenhouse gases

Please note

This page contains a limited version of this dossier in the EU Monitor.

1.

Current status

This regulation has been published on December 19, 2007 and entered into force on January  8, 2008.

2.

Key information

official title

Commission Regulation (EC) No 1497/2007 of 18 December 2007 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council, standard leakage checking requirements for stationary fire protection systems containing certain fluorinated greenhouse gases
 
Legal instrument Regulation
Number legal act Regulation 2007/1497
CELEX number i 32007R1497

3.

Key dates

Document 18-12-2007
Publication in Official Journal 19-12-2007; OJ L 333, 19.12.2007,Special edition in Croatian: Chapter 15 Volume 009
Effect 08-01-2008; Entry into force Date pub. + 20 See Art 8
End of validity 31-12-9999

4.

Legislative text

19.12.2007   

EN

Official Journal of the European Union

L 333/4

 

COMMISSION REGULATION (EC) No 1497/2007

of 18 December 2007

establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the Council, standard leakage checking requirements for stationary fire protection systems containing certain fluorinated greenhouse gases

(Text with EEA relevance)

THE COMMISSION OF THE EUROPEAN COMMUNITIES,

Having regard to the Treaty establishing the European Community,

Having regard to Regulation (EC) No 842/2006 of the European Parliament and of the Council of 17 May 2006 on certain fluorinated greenhouse gases (1), and in particular Article 3(7) thereof,

Whereas:

 

(1)

In fire protection systems comprising several interconnected containers installed in response to a specific fire risk in a defined space, the charge of fluorinated greenhouse gases should be calculated on the basis of the total charge of those containers in order to ensure that the frequency of the checks corresponds to the effective charge of fluorinated greenhouse gases.

 

(2)

Pursuant to Regulation (EC) No 842/2006, records for fire protection systems shall contain certain information. In order to ensure the effective implementation of Regulation (EC) No 842/2006, it is appropriate to provide for further information to be entered into the system records.

 

(3)

Information on the fluorinated greenhouse gas charge should be included in the system records. Where the fluorinated greenhouse gas charge is unknown, the operator of the fire protection system concerned should ensure that certified personnel determine that charge in order to facilitate the leakage checking.

 

(4)

Before the leakage check is carried out, certified personnel should carefully go through the information contained in the system records to determine any previous issues and consult previous reports.

 

(5)

In order to ensure an efficient leakage control, the leakage checks should focus on those parts of the fire protection system which are most likely to leak.

 

(6)

Where there is a presumption of a leakage, it should be followed up by a check to identify and repair it.

 

(7)

Defective installation of new systems constitutes a significant risk of leakage. Therefore, newly installed systems should be checked for leakage immediately after they have been put into service.

 

(8)

In order to ensure the effectiveness of the repair to the system, the follow up check provided for in Regulation (EC) No 842/2006 should focus on the parts of the system where leakage has been detected and on the adjacent parts.

 

(9)

The measures provided for in this Regulation are in accordance with the opinion of the Committee established by Article 18(1) of Regulation (EC) No 2037/2000 of the European Parliament and of the Council (2),

HAS ADOPTED THIS REGULATION:

Article 1

Subject matter and scope

This Regulation establishes, pursuant to Regulation (EC) No 842/2006, the standard leakage checking requirements for working and temporarily out of operation stationary systems consisting of one or more interconnected containers including associated parts installed in response to a specific fire risk in a defined space, hereinafter ‘fire protection systems’.

This Regulation shall apply to fire protection systems containing 3 kg or more of fluorinated greenhouse gases.

Article 2

System records

  • 1. 
    The operator shall indicate his name, postal address and telephone number in the records referred to in Article 3(6) of Regulation (EC) No 842/2006, hereinafter ‘system records’.
  • 2. 
    The fluorinated greenhouse gas charge for a fire protection system shall be indicated in the system records.
  • 3. 
    Where the fluorinated...

More

This text has been adopted from EUR-Lex.

 

5.

Sources and disclaimer

For further information you may want to consult the following sources that have been used to compile this dossier:

This dossier is compiled each night drawing from aforementioned sources through automated processes. We have invested a great deal in optimising the programming underlying these processes. However, we cannot guarantee the sources we draw our information from nor the resulting dossier are without fault.

 

6.

Full version

This page is also available in a full version containing the legal context, de Europese rechtsgrond, other dossiers related to the dossier at hand and the related cases of the European Court of Justice.

The full version is available for registered users of the EU Monitor by ANP and PDC Informatie Architectuur.

7.

EU Monitor

The EU Monitor enables its users to keep track of the European process of lawmaking, focusing on the relevant dossiers. It automatically signals developments in your chosen topics of interest. Apologies to unregistered users, we can no longer add new users.This service will discontinue in the near future.